Embedded sensor wires locate leaks by detecting impedance changes when insulation absorbs moisture.
During deployment, wire splicing and joint sealing quality are critical — most false alarms come from wet joints rather than pipe leakage.
Baseline impedance calibration at acceptance provides the reference for future comparison.